Acti 9 iC60H - miniature circuit breaker - 2P - 2A - C curve - A9F84202
This Acti9 iC60H is a multistandard low voltage miniature circuit breaker (MCB) with double tunnel terminals.
It is a 2P circuit breaker with 2 protected poles, 2A rated current and C tripping curve.
The rated short circuit breaking capacity goes up to 70kA at 220VAC to 240VAC conforming to EN/IEC 60947-2 standard and 10000A at 400VAC conforming to EN/IEC 60898-1 standard.
It complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2.
This miniature circuit breaker protects circuit against short circuit and overload current.
Its unique VisiTrip indicator reduces intervention time by showing the faulty circuit.
Its VisiSafe green strip guarantees the physical opening of the contacts to allow downstream maintenance.
Its fast closing mechanism independent of manual operation improves its service life.
It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles.
The Ui rated insulation voltage is 500VAC.
Its limitation class 3 (according to EN/IEC60898-1) improves downstream circuit protection cost.
The product can be clipped on a DIN rail.
Its width is 4 pitches of 9mm.
Pollution degree is 3.
Overvoltage category is IV.
The product colour is white (RAL9003).
The dimensions are (W) 36mm x (H) 85mm x (D) 78.5mm.
The weight is 0.25kg.
It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals.
The operating temperature is -35°C to 70°C.
The storage temperature is -40°C to 85°C.
Attribute | Value |
---|---|
SKU | A9F84202 |
relative humidity | 95-95 % at 55-55 °C |
ambient air temperature for storage | -40-85 °C |
overvoltage category | IV |
pollution degree | 3 conforming to EN 60947-2, 3 conforming to IEC 60947-2 |
ambient air temperature for operation | -35-70 °C |
number of protected poles | 2 |
quality labels | NF |
range of product | iC60 |
product or component type | Miniature Circuit Breaker |
net weight | 0.25 kg |
mounting mode | fixed |
standards | IEC 60898-1, IEC 60947-2, EN 60947-2, EN 60898-1 |
tropicalisation | 2 conforming to IEC 60068-1 |
earth-leakage protection | separate block |
mechanical durability | 20000 cycles |
comb busbar and distribution block compatibility | top or bottom: YES |
device short name | iC60H |
breaking capacity | 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1, 70 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2, 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2, 70 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2, 70 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2, 70 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2, 15 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 |
trip unit technology | thermal-magnetic |
range | Acti 9 |
wire stripping length | 14 mm for top or bottom connection |
[Ics] rated service breaking capacity | 70 kA 100 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz, 70 kA 100 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz, 70 kA 100 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz, 70 kA 100 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz, 7500 A 75 % conforming to EN 60898-1 - 400 V AC 50/60 Hz, 7500 A 75 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz, 70 kA 100 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz, 70 kA 100 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz, 50 kA 100 % conforming to EN 60947-2 - 440 V AC 50/60 Hz, 50 kA 100 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz, 15 kA 100 % conforming to IEC 60947-2 - 72...125 V DC, 15 kA 100 % conforming to EN 60947-2 - 72...125 V DC |
breaking capacity code | H |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2, 6 kV conforming to EN 60947-2 |
product name | Acti 9 iC60 |
network frequency | 50/60 Hz |
connections - terminals | single terminal (top or bottom) 1-25 mm² rigid, single terminal (top or bottom) 1-16 mm² flexible |
height | 85 mm |
mounting support | DIN rail |
compatibility code | iC60 |
width | 36 mm |
depth | 78.5 mm |
operating altitude | 0...2000 m |
IP degree of protection | IP20 conforming to IEC 60529, IP20 conforming to EN 60529 |
[In] rated current | 2 A |
curve code | C |
network type | AC, DC |
9 mm pitches | 4 |
poles description | 2P |
colour | white |
tightening torque | 2-2 N.m top or bottom |
electrical durability | 10000 cycles |
device application | distribution |
control type | toggle |
[Ue] rated operational voltage | 220...240 V AC 50/60 Hz, 400 V AC 50/60 Hz, 380...415 V AC 50/60 Hz, 440 V AC 50/60 Hz, 12...133 V AC 50/60 Hz, 72...125 V DC |
magnetic tripping limit | 8 x In +/- 20 % |
local signalling | trip indicator |
market segment | small commercial |
utilisation category | category A conforming to EN 60947-2, category A conforming to IEC 60947-2 |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN 60947-2, 500 V AC 50/60 Hz conforming to IEC 60947-2 |
suitability for isolation | yes conforming to IEC 60947-2, yes conforming to EN 60898-1, yes conforming to EN 60947-2, yes conforming to IEC 60898-1 |
contact position indicator | yes |
limitation class | 3 conforming to EN 60898-1, 3 conforming to IEC 60898-1 |