Acti 9 iC60N - miniature circuit breaker - 1P - 10A - C curve - A9F74110
This Acti9 iC60N is a low voltage miniature circuit breaker (MCB).
It is a 1P circuit breaker with 1 protected pole, 10A rated current and C tripping curve.
The rated short circuit breaking capacity goes up to 10kA at 220VAC to 240VAC conforming to EN/IEC 60947-2 standard and 6000A at 230VAC conforming to EN/IEC 60898-1 standard.
It complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2.
This miniature circuit breaker protects circuits against short circuit and overload current.
Its unique VisiTrip indicator reduces intervention time by showing the faulty circuit.
Its VisiSafe green strip guarantees the physical opening of the contacts to allow downstream maintenance.
Its fast closing mechanism independent of manual operation improves its service life.
It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles.
The Ui rated insulation voltage is 500VAC.
Its limitation class 3 (according to EN/IEC60898-1) improves downstream circuit protection cost.
The product can be clipped on a DIN rail.
Its width is 2 pitches of 9mm.
Pollution degree is 3.
Overvoltage category is IV.
The product colour is white (RAL9003).
The dimensions are (W) 18mm x (H) 85mm x (D) 78.5mm.
The weight is 0.215kg.
According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure.
The operating temperature is -35°C to 70°C.
The storage temperature is -40°C to 85°C.
Attribute | Value |
---|---|
SKU | A9F74110 |
relative humidity | 95-95 % at 55-55 °C |
ambient air temperature for storage | -40-85 °C |
overvoltage category | IV |
pollution degree | 3 conforming to EN 60947-2, 3 conforming to IEC 60947-2 |
ambient air temperature for operation | -35-70 °C |
number of protected poles | 1 |
range of product | iC60 |
product or component type | Miniature Circuit Breaker |
net weight | 0.215 kg |
mounting mode | fixed |
standards | IEC 60898-1, IEC 60947-2, EN 60947-2, EN 60898-1 |
tropicalisation | 2 conforming to IEC 60068-1 |
earth-leakage protection | without |
mechanical durability | 20000 cycles |
comb busbar and distribution block compatibility | top or bottom: YES |
device short name | iC60N |
breaking capacity | 36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2, 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1, 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2, 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2, 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2, 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
trip unit technology | thermal-magnetic |
range | Acti 9 |
wire stripping length | 14 mm for top or bottom connection |
[Ics] rated service breaking capacity | 27 kA 75 % conforming to EN 60947-2 - 12...60 V AC 50/60 Hz, 7.5 kA 75 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz, 27 kA 75 % conforming to IEC 60947-2 - 12...60 V AC 50/60 Hz, 7.5 kA 75 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz, 15 kA 75 % conforming to IEC 60947-2 - 100...133 V AC 50/60 Hz, 15 kA 75 % conforming to EN 60947-2 - 100...133 V AC 50/60 Hz, 6000 A 100 % conforming to EN 60898-1 - 230 V AC 50/60 Hz, 6000 A 100 % conforming to IEC 60898-1 - 230 V AC 50/60 Hz, 10 kA 100 % conforming to EN 60947-2 - 72 V DC, 10 kA 100 % conforming to IEC 60947-2 - 72 V DC, 15 kA 100 % conforming to EN 60947-2 - 12...60 V DC, 15 kA 100 % conforming to IEC 60947-2 - 12...60 V DC |
breaking capacity code | N |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2, 6 kV conforming to EN 60947-2 |
product name | Acti 9 iC60 |
network frequency | 50/60 Hz |
connections - terminals | single terminal (top or bottom) 1-25 mm² rigid, single terminal (top or bottom) 1-16 mm² flexible |
height | 85 mm |
mounting support | DIN rail |
compatibility code | iC60 |
width | 18 mm |
depth | 78.5 mm |
operating altitude | 0...2000 m |
IP degree of protection | IP20 conforming to IEC 60529, IP20 conforming to EN 60529 |
[In] rated current | 10 A |
curve code | C |
network type | AC, DC |
9 mm pitches | 2 |
poles description | 1P |
colour | white |
tightening torque | 2-2 N.m top or bottom |
electrical durability | 10000 cycles |
device application | distribution |
control type | toggle |
[Ue] rated operational voltage | 230 V AC 50/60 Hz, 220...240 V AC 50/60 Hz, 12...60 V AC 50/60 Hz, 100...133 V AC 50/60 Hz, 72 V DC, 12...60 V DC |
magnetic tripping limit | 8 x In +/- 20 % |
local signalling | trip indicator |
utilisation category | category A conforming to EN 60947-2, category A conforming to IEC 60947-2 |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN 60947-2, 500 V AC 50/60 Hz conforming to IEC 60947-2 |
suitability for isolation | yes conforming to IEC 60947-2, yes conforming to EN 60898-1, yes conforming to EN 60947-2, yes conforming to IEC 60898-1 |
contact position indicator | yes |
limitation class | 3 conforming to EN 60898-1, 3 conforming to IEC 60898-1 |