Acti 9 iDPN N Vigi - RCBO - 1P+N - 16A - C Curve - 6000A - 30mA - type AC - A9D31616
This Acti9 iDPN Vigi is a modular residual current breaker with overcurrent protection (RCBO).
It is a 1P+N circuit breaker with 1 protected pole, 16A In rated current and C tripping curve.
The earth leakage protection class is AC type with a sensitivity of 30mA.
The earth-leakage protection time delay is instantaneous.
The Icn rated short circuit breaking capacity is up to 6000A according EN/IEC 61009-2-1 standard.
This product protects against short circuit, cable overload, electrical shock by indirect contact and fire hazards.
Its earth fault indicator on front face allows quick identification of the type of default.
It has a longer service life thanks to its high limitation and fast closing.
It has a test button.
This product is compliant with EN/IEC 61009-2-1 standard.
It has an electrical endurance going up to 20000 cycles and a mechanical endurance going up to 20000 cycles.
The Ue operational voltage is 220VAC to 240VAC.
The Ui rated insulation voltage is 400VAC.
The Uimp rated impulse withstand voltage is 4kV.
The frequency is 50Hz.
It is DIN rail mountable.
The width in 9mm pitches is 4.
The product color is white (RAL9003).
The dimensions are (W) 36mm x (H) 85mm x (D) 73mm.
The weight is 125g.
According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure.
The operating temperature is from -5°C to 60°C.
The storage temperature is from -40°C to 85°C.
Attribute | Value |
---|---|
SKU | A9D31616 |
product certifications | GOST, VDE |
relative humidity | 95-95 % at 55-55 °C |
ambient air temperature for storage | -40-85 °C |
overvoltage category | III conforming to IEC 60364 |
pollution degree | 3 |
ambient air temperature for operation | -5-60 °C |
number of protected poles | 1 |
range of product | iDPN Vigi |
product or component type | Pengaman Arus Bocor |
net weight | 125 g |
mounting mode | clip-on |
standards | EN/IEC 61009-2-1 |
tropicalisation | 2 conforming to IEC 60068-1 |
earth-leakage protection | integrated |
mechanical durability | 20000 cycles |
comb busbar and distribution block compatibility | top or bottom: YES |
device short name | iDPN N Vigi |
breaking capacity | 6000 A Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 |
trip unit technology | thermal-magnetic |
range | RCBO |
wire stripping length | 15 mm for top or bottom connection |
[Ics] rated service breaking capacity | 6000 A 100 % x Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 |
[Uimp] rated impulse withstand voltage | 4 kV |
product name | Acti 9 iDPN Vigi |
electromagnetic compatibility | 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1 |
rated breaking and making capacity | Idm 6000 A at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1 |
earth-leakage protection class | type AC |
earth-leakage sensitivity | 30 mA |
device location in system | outgoer |
network frequency | 50 Hz |
connections - terminals | single terminal top or bottom 1-16 mm² rigid, single terminal top or bottom 1-10 mm² flexible, single terminal top or bottom 1-10 mm² flexible with ferrule |
height | 85 mm |
mounting support | DIN rail |
compatibility code | iDPN |
width | 36 mm |
depth | 73 mm |
IP degree of protection | IP20 conforming to IEC 60529, IP40 (modular enclosure) conforming to IEC 60529 |
[In] rated current | 16 A |
curve code | C |
network type | AC |
9 mm pitches | 4 |
poles description | 1P + N |
colour | white |
tightening torque | 2-2 N.m top or bottom |
electrical durability | 20000 cycles |
device application | distribution |
control type | toggle |
[Ue] rated operational voltage | 220...240 V AC 50 Hz |
magnetic tripping limit | 5...10 x In |
local signalling | ON, OFF, fault trip |
market segment | small commercial, residential |
[Ui] rated insulation voltage | 400 V AC 50 Hz |
suitability for isolation | yes conforming to EN/IEC 60947-2 |
earth-leakage protection time delay | instantaneous |
neutral position | left |
contact position indicator | yes |
limitation class | 3 conforming to EN/IEC 61009-2-1 |
residual current tripping technology | voltage independent |
locking options description | padlocking device |