Acti 9 iID - RCCB - 2P - 40A - 30mA - type AC - A9R71240
This Acti9 iID is a modular and reliable residual current circuit breaker (RCCB).
It is a 2P circuit breaker with In rated current of 40A, AC type protection class and a 30mA earth leakage sensitivity.
This product protects against electrical shock by direct or indirect contact and fire hazards.
It performs the function of disconnection of electrical circuits in case of earth fault.
Its unique Visitrip indicator reduces intervention time by showing the faulty device with a mechanical indicator on front face.
This product also has a VisiSafe window with a green strip on the toggle indicating full opening of the poles allowing downstream maintenance This product is compliant with EN/IEC 61008-1 standard.
The (Im/IΔm) rated breaking and making short circuit capacity is 1500A.
The (Inc/IΔc) conditional rated short circuit current is 10kA.
The electrical endurance is up to 15000 cycles.
The mechanical endurance is up to 20000 cycles.
The Ue operational voltage is 220VAC to 240VAC.
The Ui rated insulation voltage is 500VAC.
The Uimp rated impulse withstand voltage is 6kV.
The frequency is 50Hz or 60Hz.
It is DIN rail mountable.
The width in 9mm pitches is 4.
The product colour is white (RAL9003).
The dimensions are (W) 36mm x (H) 91mm x (D) 73.5mm.
The weight is 0.21kg.
It has an IP20 degree of protection.
It becomes IP40 once in modular enclosure according to IEC/EN 60529 standard.
The operating temperature is from -5°C to 60°C.
The storage temperature is from -40°C to 85°C.
Attribute | Value |
---|---|
SKU | A9R71240 |
product certifications | SNI |
ambient air temperature for storage | -40-85 °C |
pollution degree | 3 |
ambient air temperature for operation | -5-60 °C |
range of product | iID |
product or component type | Pengaman Arus Bocor |
net weight | 0.21 kg |
mounting mode | clip-on |
standards | EN/IEC 61008-1 |
mechanical durability | 20000 cycles |
comb busbar and distribution block compatibility | top or bottom: tooth |
device short name | iID |
range | RCCB |
wire stripping length | 14 mm for top or bottom connection |
[Uimp] rated impulse withstand voltage | 6 kV |
product name | Acti 9 iID |
electromagnetic compatibility | 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61008-1 |
rated breaking and making capacity | Idm 1500 A, Im 1500 A |
earth-leakage protection class | type AC |
earth-leakage sensitivity | 30 mA |
device location in system | outgoer |
network frequency | 50/60 Hz |
connections - terminals | single terminal top or bottom 1-35 mm² rigid, single terminal top or bottom 1-25 mm² flexible, single terminal top or bottom 1-25 mm² flexible with ferrule |
height | 91 mm |
mounting support | DIN rail |
compatibility code | iID |
width | 36 mm |
depth | 73.5 mm |
IP degree of protection | IP20 conforming to IEC 60529, IP40 (modular enclosure) conforming to IEC 60529 |
[In] rated current | 40 A |
network type | AC |
9 mm pitches | 4 |
poles description | 2P |
colour | white |
tightening torque | 3.5-3.5 N.m top or bottom |
electrical durability | AC-1: 15000 cycles |
control type | toggle |
[Ue] rated operational voltage | 220...240 V AC 50/60 Hz |
[Ui] rated insulation voltage | 500 V AC 50/60 Hz |
earth-leakage protection time delay | instantaneous |
neutral position | left |
contact position indicator | yes |
rated conditional short-circuit current | 10 kA |
residual current tripping technology | voltage independent |
locking options description | padlocking device |