Acti 9 iTL impulse relay - 2P - 1NO+1NC - 16A - coil 110 VDC - 230...240 VAC 50/60Hz - A9C30815
This Acti9 iTLi is a modular impulse relay.
It is a changeover contact with 1 normally open and 1 normally close contact.
Rated current is 16A, 24VAC to 250VAC operating voltage and it operates with 230VAC to 240VAC or 110VDC control voltage.
Electrical endurance goes up to 200000 cycles for AC-21 or 100000 cycles for AC-22.
The switching frequency is 5 switching operations/minute or 100 switching operations/day.
The duration of the command order should be between 50ms to 1s.
It is mainly used for lighting control applications.
The Ui rated insulation voltage is 440VAC.
The Uimp rated impulse withstand voltage is 6kV.
The operating frequency is 50Hz or 60Hz.
It is DIN rail mountable.
Pollution degree is 3.
Overvoltage category is IV.
The dimensions are (W) 18mm x (H) 84mm x (D) 60mm.
The degree of protection is IP20 and IP40 in an enclosure.
The operating temperature is from -20°C to 50°C.
The storage temperature is from -40°C to 70°C.
This product is compliant with IEC/EN 60669-1 and IEC/EN 60669-2-2 standard.
Attribute | Value |
---|---|
SKU | A9C30815 |
product certifications | CCC, GOST |
relative humidity | 95-95 % at 55-55 °C |
ambient air temperature for storage | -40-70 °C |
pollution degree | 3 |
ambient air temperature for operation | -20-50 °C |
quality labels | IMQ, NF, KEMA, VDE, CEBEC |
range of product | iTL |
product or component type | Miniature Circuit Breaker |
mounting mode | fixed |
standards | EN 669-1, EN 669-2-2 |
tropicalisation | 2 |
device short name | iTLi |
range | Command Control |
wire stripping length | 11 mm |
[Uc] control circuit voltage | 110 V DC, 230...240 V AC 50/60 Hz |
range compatibility | iATEt, iATLc, iATLc+s, iATLm, iATLs, iETL iTL 16, iATLc+c, iATL4, iATLz, iATL24 |
product name | Acti 9 iTL |
pole contact composition | 1 NO + 1 NC |
network frequency | 50/60 Hz |
connections - terminals | control circuit: tunnel type terminals 1 cable(s) 0.5-4 mm² rigid, control circuit: tunnel type terminals 1 cable(s) 0.5-4 mm² rigid with cable end, control circuit: tunnel type terminals 1 cable(s) 1-4 mm² flexible, control circuit: tunnel type terminals 1 cable(s) 1-4 mm² flexible with ferrule, power circuit: tunnel type terminals 1 cable(s) 1.5-4 mm² rigid, power circuit: tunnel type terminals 1 cable(s) 1.5-4 mm² rigid with cable end, power circuit: tunnel type terminals 1 cable(s) 1.5-4 mm² flexible, power circuit: tunnel type terminals 1 cable(s) 1.5-4 mm² flexible with ferrule |
height | 84 mm |
mounting support | DIN rail |
compatibility code | iTLi |
width | 18 mm |
depth | 60 mm |
IP degree of protection | IP20 conforming to IEC 60529 (on opening), IP40 conforming to IEC 60529 (in enclosure) |
[In] rated current | 16 A |
network type | AC |
9 mm pitches | 2 |
poles description | 2P |
tightening torque | 1-1 N.m |
electrical durability | AC-21: 200000 cycles, AC-22: 100000 cycles |
device application | changeover relay |
control type | remote and manual control, coil deconnection |
[Ue] rated operational voltage | 250 V AC 50/60 Hz |
local signalling | ON/OFF indication |
market segment | small commercial, residential |
impulse duration | 50 ms...1 s |
control signal type | impulse |
noise level | 60 dB |
switching frequency | 100 switching operations/day, 5 switching operations/minute |
remote control type | illuminated push-button 3 mA |