Schneider Electric

Altivar Easy 610 variable speed drive ATV610 - 110 kW / 150HP - 380...415 V - IP20 - ATV610C11N4

Out of stock
SKU
ATV610C11N4
45%
Special Price Rp 92.237.099 Regular Price Rp 167.703.817
Details

This product is part of the Modicon TM3 range, an offer of expansion I/O modules for Modicon M221, M241, M251 and M262.

The analogue output module provides 2 outputs with 11bit + sign and 12bit resolution.

It is an output module with a rated supply voltage of 24V DC and a current consumption of 70mA at 24V DC via external supply full load.

This product is capable of controlling variable speed drives or any device equipped with a current or voltage input.

There is an insulation between output and supply at 1500V AC, output and internal logic at 500V AC.

It is furnished with removable screw terminal for electrical connection with 5.08mm pitch adjustment for outputs.

It is an IP20 rated product.

Its dimensions are 23.6mm (Width) x 70mm (Depth) x 90mm (Height).

It weighs 0.115kg.

This product is certified by CE.

It meets EN/IEC 61131-2 and EN/IEC 61010-2-201 standards.

This module is compatible with Modicon M262, Modicon M241, Modicon M251 and Modicon M221 logic controller.

It supports top hat type TH35-15, top hat type TH35-7.5 rail conforming to IEC 60715 and plate or panel with fixing kit mount.

Modicon TM3 expansion modules have been designed with a simple interlocking assembly mechanism.

A bus expansion connector is used to distribute data and the power supply when assembling the Modicon TM3 modules with logic controllers.

Boost the performance of your controller with the Modicon TM3 I/O system specially designed for the Modicon M221, M241 and M251 logic controllers.

More Information
More Information
Attribute Value
SKU ATV610C11N4
relative humidity 5-95 % without condensation conforming to IEC 60068-2-3
pollution degree 2 conforming to EN/IEC 61800-5-1
ambient air temperature for operation -15-45 °C (without derating), 45-60 °C (with derating factor)
environmental characteristic chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3, dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3
motor power hp 150 hp for normal duty, 125 hp for heavy duty
continuous output current 211 A at 2.5 kHz for normal duty, 173 A at 2.5 kHz for heavy duty
isolation between power and control terminals
output frequency 1.0E-4-0.5 kHz
output voltage <= power supply voltage
range of product Easy Altivar 610
operating position vertical +/- 10 degree
product or component type Soft Starter & Variable Speed Drive
net weight 82 kg
mounting mode cabinet mount
standards EN/IEC 61800-3, EN/IEC 61800-5-1, IEC 60721-3, environment 2 category C3 EN/IEC 61800-3
device short name ATV610
range Altivar Easy ATV610
minimum switching current relay output R1, R2, R3: 5 mA at 24 V DC
insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
[Us] rated supply voltage 380...460 V - 15...10 %
electromagnetic compatibility electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2, radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3, electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4, 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5, conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
analogue input type AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution 12 bits, AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits, AI2, AI3 software-configurable temperature probe or water level sensor
refresh time relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
electrical connection control, screw terminal: 0.5...1.5 mm², line side, screw terminal: 2 x 50...3 x 120 mm², motor, screw terminal: 3 x 50...3 x 120 mm²
line current 201 A at 380 V (normal duty), 175.7 A at 460 V (normal duty), 170 A at 380 V (heavy duty), 149.1 A at 460 V (heavy duty)
asynchronous motor control profile variable torque standard, constant torque standard, optimized torque mode
variant standard version
relay output number 3
maximum transient current 232 A during 60 s (normal duty), 260 A during 60 s (heavy duty)
input compatibility DI1...DI6: logic input level 1 PLC conforming to EN/IEC 61131-2, DI5, DI6: pulse input level 1 PLC conforming to IEC 65A-68
analogue output number 2
nominal switching frequency 2.5 kHz
braking to standstill by DC injection
height 852 mm, 1159 mm with IP21 conformity kit
power dissipation in W 2026 W(forced convection) at 380 V, switching frequency 2.5 kHz
marking CE
width 320 mm
depth 390 mm
vibration resistance 1.5 mm peak to peak (f= 2-13 Hz) conforming to IEC 60068-2-6, 1 gn (f= 13-200 Hz) conforming to IEC 60068-2-6
operating altitude <= 1000 m without derating, 1000...4800 m with current derating 1 % per 100 m
IP degree of protection IP20
product destination asynchronous motors
local signalling 2 LEDs for local diagnostic, 1 LED (yellow) for embedded communication status, 2 LEDs (dual colour) for communication module status, 1 LED (red) for presence of voltage
protection type thermal protection: motor, thermal protection: drive, overheating: drive, line supply overvoltage: drive, line supply undervoltage: drive, break on the control circuit: drive, motor phase break: motor, overcurrent between output phases and earth: drive, overload of output voltage: drive, short-circuit protection: drive, motor phase break: drive, overvoltages on the DC bus: drive, line supply phase loss: drive, overspeed: drive
connector type 1 RJ45 (on the remote graphic terminal) for Modbus serial
motor power kW 110 kW for normal duty, 90 kW for heavy duty
supply frequency 50...60 Hz +/-5 %
shock resistance 6 gn for 11 ms conforming to IEC 60068-2-27
network number of phases 3 phases
communication port protocol Modbus serial
product specific application fan, pump, compressor, conveyor
analogue output type software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits, software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits
maximum switching current relay output R1, R2, R3 on resistive load, cos phi = 1 : 3 A at 250 V AC, relay output R1, R2, R3 on resistive load, cos phi = 1 : 3 A at 30 V DC, relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC, relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
noise level 76 dB conforming to 86/188/EEC
discrete input type DI1...DI6 programmable as logic input, 24 V DC (<= 30 V), impedance: 3.5 kOhm, DI5, DI6 programmable as pulse input: 0-30 kHz, 24 V DC (<= 30 V)
physical interface 2-wire RS 485 for Modbus serial
type of cooling forced convection
discrete input number 6
transmission rate 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
discrete input logic 16 preset speeds, positive logic (source): DI1...DI6 configurable logic input, < 5 V (state 0), > 11 V (state 1), negative logic (sink): DI1...DI6 configurable logic input, > 16 V (state 0), < 10 V (state 1), positive logic (source): DI5, DI6 configurable pulse input, < 0.6 V (state 0), > 2.5 V (state 1)
prospective line Isc 50 kA
acceleration and deceleration ramps S, U or customized, linear adjustable separately from 0.01 to 9000 s
transmission frame RTU for Modbus serial
apparent power 140.0 kVA at 460 V (normal duty), 118.8 kVA at 460 V (heavy duty)
type of polarization no impedance for Modbus serial
relay output type configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles, configurable relay logic R2: sequence relay NO electrical durability 100000 cycles, configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input, +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
switching frequency 1...8 kHz adjustable
analogue input number 3
motor slip compensation can be suppressed, adjustable, not available in permanent magnet motor law, automatic whatever the load
method of access slave
number of addresses 1-247 for Modbus serial
linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input, AQ1, AQ2: +/- 0.2 % for analog output
EMC filter integrated conforming to EN/IEC 61800-3 category C3 with 50 m
sampling duration 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input, 2 ms +/- 0.5 ms (DI1...DI6)configurable - discrete input, 5 ms +/- 1 ms (DI5, DI6)configurable - pulse input, 10 ms +/- 1 ms (AQ1, AQ2) - analog output
option card slot A: communication card, Profibus DP V1, slot A: digital or analog I/O extension card, slot A: relay output card
frequency resolution display unit: 0.1 Hz, analog input: 0.012/50 Hz
supply external supply for digital inputs: 24 V DC (19-30 V), <1.25 mA, protection type: overload and short-circuit protection, internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
PT. Telesindo Citra Sejahtera © 2021 All Rights Reserved.