Schneider Electric

PM5330 powermeter w modbus - upto 31st H - 256K 2DI/2DO 35alarms - flush mount - METSEPM5330

In stock
SKU
METSEPM5330
33%
Special Price Rp 9.305.918 Regular Price Rp 13.889.430
Details

This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display.

The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 64 samples per cycle.

The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to the 31st Harmonic.

Include 256 kiloBytes of memory for two fixed parameters, active and reactive energy.

The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 415 VAC and 125 to 250 VDC.

Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations.

The range of measurement voltage between Phases is 35 to 690 VAC at 47 to 63 Hz.

Measurement range between Phase and Neutral is 20 to 400VAC at 47 to 63 Hz.

Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support.

The meter also has two digital inputs or digital outputs, configurable, and dual relay outputs.

There are 35 configurable alarms and it supports four tariff schedules.

Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 2.83 inches (72 millimetres), height 3.78 inches (96 millimetres) and product weight 15.2 onces (430 g).

More Information
More Information
Attribute Value
SKU METSEPM5330
product certifications CE conforming to IEC 61010-1, cULus conforming to UL 61010-1
relative humidity 5-95 % at 50-50 °C
ambient air temperature for storage -40-85 °C
pollution degree 2
ambient air temperature for operation -25-70 °C
product or component type Meter & Manajemen Energi
net weight 430 g
mounting mode flush-mounted
standards IEC 60529, UL 61010-1, EN 50470-3, IEC 61557-12, IEC 62053-22, IEC 62053-24, EN 50470-1
device short name PM5330
range Power Meter
product name PowerLogic PM5000
[Us] rated supply voltage 125...250 V DC, 100...415 V AC 45...65 Hz
electromagnetic compatibility limits for harmonic current emissions class A conforming to IEC 61000-3-2, conducted RF disturbances level 3 conforming to IEC 61000-4-6, magnetic field at power frequency level 4 conforming to IEC 61000-4-8, conducted and radiated emissions class B conforming to EN 55022, electrostatic discharge level 4 conforming to IEC 61000-4-2
type of measurement voltage, current, frequency, power factor, energy, active and reactive power
analogue input type voltage (impedance 5 MOhm), current (impedance 0.3 mOhm)
memory capacity 256 kB
network frequency 50 Hz, 60 Hz
connections - terminals voltage circuit: screw terminal block4, control circuit: screw terminal block2, current transformer: screw terminal block6, input/output circuit: screw terminal block6, relay output: screw terminal block4, Ethernet network: RJ45 connector
height 96 mm
mounting support framework
compatibility code PM5330
width 96 mm
depth 72 mm
operating altitude 2000 m
IP degree of protection IP30 body: conforming to IEC 60529, IP52 front: conforming to IEC 60529
[In] rated current 1 A, 5 A
poles description 1P + N, 3P, 3P + N
device application power monitoring, multi-tariff
market segment buildings small building cost management: billing: main incomer, buildings small building cost management: billing: sub feeder, buildings medium building cost management: billing: main incomer, buildings medium building cost management: billing: sub feeder, buildings large building cost management: billing: main incomer, buildings large building cost management: billing: sub feeder, buildings multi-site cost management: billing: main incomer, buildings multi-site cost management: billing: sub feeder, datacenter cost management: billing: main incomer, datacenter cost management: billing: sub feeder, healthcare cost management: billing: main incomer, healthcare cost management: billing: sub feeder, industry cost management: billing: main incomer, industry cost management: billing: sub feeder, buildings small building cost management: cost allocation: main incomer, buildings small building cost management: cost allocation: sub feeder, buildings medium building cost management: cost allocation: main incomer, buildings medium building cost management: cost allocation: sub feeder, buildings large building cost management: cost allocation: main incomer, buildings large building cost management: cost allocation: sub feeder, buildings multi-site cost management: cost allocation: main incomer, buildings multi-site cost management: cost allocation: sub feeder, datacenter cost management: cost allocation: main incomer, datacenter cost management: cost allocation: sub feeder, healthcare cost management: cost allocation: main incomer, healthcare cost management: cost allocation: sub feeder, industry cost management: cost allocation: main incomer, industry cost management: cost allocation: sub feeder, buildings small building network management: main incomer, buildings small building network management: sub feeder, buildings medium building network management: main incomer, buildings medium building network management: sub feeder, buildings large building network management: sub feeder, buildings multi-site network management: sub feeder, datacenter network management: sub feeder, healthcare network management: sub feeder, industry network management: sub feeder
measurement voltage 20-400 V AC 45...65 Hz between phase and neutral, 35-690 V AC 45...65 Hz between phases
display type backlit LCD
maximum power consumption in VA 10 VA at 415 V
measurement current 10-9000 mA
frequency measurement range 45-65 Hz
communication port support RS485
power quality analysis up to the 31st harmonic
sampling rate 64 samples/cycle
number of outputs 2 digital, 2 relay
communication port protocol Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V, JBUS
number of inputs 2 digital
information displayed tariff (4)
measurement accuracy voltage +/- 0.5 %, current +/- 0.5 %, frequency +/- 0.05 %, apparent power +/- 0.5 %, active energy +/- 0.5 %, active power +/- 0.5 %, power factor +/- 0.005, reactive energy +/- 2 %
data recording time stamping, event logs, maintenance logs, min/max of instantaneous values, data logs, alarm logs
accuracy class class 0.5S active energy conforming to IEC 62053-22
display resolution 128 x 128 pixels
ride-through time 80 ms 120 V AC typical, 100 ms 230 V AC typical, 100 ms 415 V AC typical